Ductwork sizing, calculation and design for efficiency

Guide to designing ductwork systems

22
how to design a duct system ws

How to design a duct system. In this article we’ll be learning how to size and design a ductwork system for efficiency. We’ll include a full worked example as well as using CFD simulations to optimise the performance and efficiency using SimScale. Scroll to the bottom to watch the FREE YouTube video tutorial!

🏆🏆🏆 Create a free SimScale account to test the cloud-based CFD simulation platform here: https://www.simscale.com/ With 100,000+ users worldwide, SimScale is a revolutionary cloud-based CAE platform that gives instant access to CFD and FEA simulation technology for quick and easy virtual testing, comparison and optimization of designs in several industries, including HVAC, AEC, and electronics.

Methods of ductwork design

There are many different methods used to design ventilation systems, the most common ways being:

  • Velocity reduction method: (Residential or small commercial installations)
  • Equal friction method: (Medium to large sized commercial installations)
  • Static regain: Very large installations (concert halls, airports and industrial)

We’re going to focus on the equal friction method in this example as it’s the most common method used for commercial HVAC systems and its fairly simple to follow.

Design example

The Building Layout - how to design a duct system
The Building Layout

So we’ll jump straight into designing a system. We’ll use a small engineering office as an example and we want to make a layout drawing of the building which we’ll use for the design and calculations. This is a really simple building it has just 4 offices a corridor and a mechanical room which is where the fan, filters and air heater or cooler will be located.

Building heating and cooling loads - duct sizing
Building heating and cooling loads

The first thing we need to do is calculate the heating and cooling loads for each room. I won’t cover how to do that in this article we’ll have to cover that in a separate tutorial as it’s a separate subject area.

Once you have these, just tally them together to find which is the biggest Load as we need to size the system to be able to operate at the peak demand. The cooling load is usually the highest, as it is in this case.

Now we need to convert the cooling loads into volume flow rates but to do that we first need to convert this to mass flow rate so we use the formula:

mdot = Q / (cp x Δt)

Calculate air mass flow rate from cooling load
Calculate air mass flow rate from cooling load

Where mdot means mass flow rate (kg/s), the Q being the cooling load of the room (kW), cp is the specific heat capacity of the air (kJ/kg.K) and Δt being the temperature difference between the designed air temperature and the design return temperature. Just to note that we will use a cp of 1.026 kJ/kg.k as standard and the delta T should be less than 10*C so we’ll use 8*c.

We know all the values for this so we can calculate the mass flow rate (how many kilograms per second of air needs to enter the room). If we look at the calculation for room 1, we see it requires 0.26 kg/s. So we just repeat that calculation for the rest of the room to find all the mass flow rates.

Air mass flow rate calculation for each room
Air mass flow rate calculation for each room

Now we can convert these into volume flow rates. To do that we need the specific volume or density of the air. We’ll specify 21*c and assume atmospheric pressure of 101.325 kPa. We can look this up in our air properties tables but I like to just use an online calculator http://bit.ly/2tyT8yp as its quicker. So we just drop those numbers in and we get the density of air being 1.2 kg/m3.

You see that density has the units of kg/m3 but we need specific volume which is m3/kg so to convert that we just take the inverse which means to calculate 1.2 to the power of -1. You can just do that in excel very quickly (copy paste this =1.2^-1) to get the answer of 0.83m3/kg.
Now that we have that we can calculate the volume flow rate using the formula:

vdot = mdot multiplied by v.

Calculate air volume flow rate from mass flow rate
Calculate air volume flow rate from mass flow rate

where vdot equals the volume flow rate, mdot equals the mass flow rate of the room and v equals the specific volume which we just calculated.
So if we drop those values in for room 1 we get a volume flow rate of 0.2158m3/s that is how much air needs to enter the room to meet the cooling load. So just repeat that calculation for all the rooms.

Building air volume flow rates - duct sizing
Building air volume flow rates – duct sizing

Now we’re going to sketch out our ductwork route onto the floor plan so we can start to size it.

Ductwork layout - ductwork design
Ductwork layout

Before we go any further we need to consider some things which will play a big role in the overall efficiency of the system.

Design considerations

The first one being the shape of the ductwork. Ductwork comes in round, rectangular and flat-oval shape. Round duct is by far the most energy efficient type and that’s what we’ll use in our worked example later on. If we compare round duct to rectangular duct we see that:

Round duct and rectangular duct comparison
Round duct and rectangular duct comparison

A round duct with a cross sectional area of 0.6m2 has a perimeter of 2.75m
A rectangular duct with an equal cross sectional area has a perimeter of 3.87m
The rectangular duct therefore requires more metal for its construction, this adds more weight and costs to the design. The larger perimeter also means more air will come into contact wit the material and this adds friction to the system. Friction in a system means the fan needs to work harder and this results in higher operating costs. Always use round duct where possible although in many cases rectangular duct needs to be used as space is limited.

Ductwork pressure drop
Ductwork pressure drop

The second thing to consider is the material being used for the ducts, and the roughness of this material as this causes friction. For example, if we had two ducts, with equal dimensions, volume flow rate and velocity, the only difference is the material. One is made from standard galvanised steel the other from fibreglass, the pressure drop over a 10m distance for this example, is around 11 Pa for the galvanised steel and 16 Pa for the Fibreglass.

Energy efficient duct fittings
Energy efficient duct fittings

The third thing we have to consider is the dynamic losses caused by the fittings. We want to use the smoothest fittings possible for energy efficiency. For example use long radius bends rather than right angles as the sudden change in direction wastes a huge amount of energy.

Ductwork CFD simulations
Ductwork CFD simulations

We can compare the performance of different ductwork designs, quickly and easily using CFD or computational fluid dynamics. These simulations were produced using a revolutionary cloud based CFD and FEA engineering platform, by SimScale, who have kindly sponsored this article.
You can access this software free of charge by clicking here, and they offer a number of different account types depending on your simulation needs.

SimScale is not just limited to ductwork design, it’s also used for data centers, AEC applications, electronics design, as well as thermal and structural analysis.

Just a quick look on their site and you can find thousands of simulations for everything from buildings, HVAC systems, heat exchangers, pumps and valves to race cars and air planes, which can all be copied and used as templates for your own design analysis.

They also offer free webinars, courses and tutorials to help you set up and run your own simulations. If like me you have some experience creating CFD simulations then you’ll know that this type of software is usually very expensive and you would also need a powerful computer to run it.

With SimScale, however, all can be done from a web browser. As the platform is cloud-based, their servers do all the work and we can access our design simulations from anywhere, which makes our lives as engineers a lot easier.

So if you’re an engineer, designer, architect or just someone interested in trying out simulation technology, then I highly recommend you check this software out, get your free account by following this link.

CFD ductwork design standard and optimised
CFD ductwork design standard and optimised

Now if we look at the comparison for the two designs we have a standard design on the left and a more efficient design on the right which has been optimised using simscale. Both designs use an air velocity of 5m/s, the colours represent the velocity with blue meaning low velocity and red representing the high velocity regions.

Ductwork standard design
Ductwork standard design

We can see from the velocity colour scale and the streamlines that in the design on the left, the inlet air directly strikes the sharp turns that are present in the system which causes an increase in the static pressure. The sharp turns cause a large amount of recirculation regions within the ducts, preventing the air from moving smoothly.

The tee section at the far end of the main duct causes the air to suddenly divide and change direction. There is a high amount of backflow here which again increases the static pressure and reduces the amount of air delivery

The high velocity in the main duct which is caused by the sharp turns and sudden bends, reduces the flow into the 3 branches on the left.

Ductwork optimised design energy efficient
Ductwork optimised design energy efficient

If we now focus on the optimised design on the right, we see the fittings used follow a much smoother profile with no sudden obstructions, recirculation or backflow which significantly improves the air flow rate within the system. At the far end of the main duct the air is divided into two branches through a gentle, curved tee section. This allows the air to smoothly change direction and thus there is no sudden increase in static pressure and the air flow rate to the rooms has dramatically increased.

The three branches within the main duct now receive equal air flow making a significant improvement to the design. This is because an additional branch now feeds the three smaller branches allowing some of the air to smoothly break away from the main flow and feed into these smaller branches.

With these considerations in place we can come back to the duct design.

Duct and fitting lables - duct sizing
Duct and fitting labels

Now we need to label every section of ductwork as well as the fittings with a letter. Notice we are only designing a very simple system here so I’ve only included ducts and basic fittings, I’ve not included things such as grilles, inlets, flexible connections, fire dampers etc.

Now we want to make a table with the rows labelled as per the example. Each duct and fitting needs its own row, if the air stream splits such as with a Tee section, then we need to include a line for each direction, we’ll see that later in the article.

Just add in the letters to separate rows then declare what type of fitting or duct that corresponds to.

Ductwork chart air flow rate
Ductwork chart air flow rate

We can start to fill some of the data in, we can first include the volume flow rates for each of the branches, this is easy as its just the volume flow rate for the room which it serves. You can see on the chart I’ve filled that in.

Ductwork chart main duct flow rates
Ductwork chart main duct flow rates

Then we can start to size the main ducts. To do this make sure you start at the main duct which is furthest away. Then we just add up the volume flow rates for all the branches downstream of this. For the main duct G we just sum branches L and I. For D that’s just the sum of L I and F and for duct A its then the sum of L, I, F and C. so just enter those into the table.

From the rough drawing we measure out the length of each duct section and enter this into the chart.

Duct sizing – How to size ductwork

To size the ducts you’re going to need a duct sizing chart. You can obtain these from ductwork manufacturers or from industry bodies such as CIBSE and ASHRAE. If you don’t have one, you can find them in the following links. Link 1 and Link 2

These charts hold a lot of information. We can use them to find the pressure drop per meter, the air velocity, the volume flow rate and also the size of the ductwork. The layout of the chart does vary a little depending on the manufacturer but in this example the vertical lines are for pressure drop per meter of duct. The horizontal lines are for volume flow rate. The downward diagonal lines are for velocity, the upward diagonal lines are for duct diameter.

We start sizing from the first main duct which is section A. To limit the noise in this section we’ll specify that it can only have a maximum velocity of 5m/s. We know that this duct also requires a volume flow rate of 0.79m3/s so we can use the velocity and volume flow rate to find the missing data.

Duct sizing example
Duct sizing example

We take the chart and scroll up from the bottom left until we hit the volume flow rate of 0.79m3/s. Then we locate where the velocity line is of 5m/s and we draw a line across until we hit that. Then to find the pressure drop we draw a vertical line down from this intersection. In this instance we see it comes out at 0.65 pa per meter. So add this figure into the chart. As we’re using the equal pressure drop method we can use this pressure drop for all the duct lengths so fill those in too. Then we scroll up again and align our intersection with the upward diagonal lines to see this requires a duct with a diameter of 0.45m so we add that into the table also.

We know the volume flow rate and pressure drop so we can now calculate the values for section C and then the remaining ducts.

For the remainder of the ducts we use the same method.

Duct sizing equal pressure method
Duct sizing equal pressure method

On the chart we start by drawing a line from 0.65 pa/m all the way up and then draw a line across from our required volume flow rate, in this case for section C we need 0.21m3/s. At this intersection we draw a line to find the velocity and we can see that it falls within the lines of 3 and 4m/s so we need to estimate the value, in this case it seems to be about 3.6m/s so we add that to the chart. Then we draw another line on the other diagonal grid to find our duct diameter which in this case is about 0.27m and we’ll add that to the table too.

Repeat that last process for all the remaining ducts and branches until the table is complete.

Now find the total duct losses for each duct and branch, that’s very easy to do simply multiply the duct length by the pressure drop per meter, in our example we found it to be 0.65pa/m. Do that for all the ducts and branches on the table.

Sizing ductwork fittings

The first fitting we’ll look at is the 90* bend between ducts J and L

For this we look up our loss coefficient for the bend from the manufacturer or the industry body, you can find that by clicking this link.

Duct bend fitting pressure loss coefficient
Duct bend fitting pressure loss coefficient

In this example we can see the coefficient comes out at 0.11

We then need to calculate the dynamic loss caused by the bend changing the direction of flow. For that we use the formula Co multiplied by rho multiplied by v squared divided by 2 where co is our coefficient, rho is the density of the air and v is the velocity.

Duct bend pressure loss formula
Duct bend pressure loss formula

We already know all these values so if we drop the figures in we get an answer of 0.718 pascals. So just add that to the table. (Watch the video at the bottom of the page to see how to calculate that).

Duct tee pressure loss
Duct tee pressure loss

The next fitting we’ll look at is the tee which connects the main duct to the branches, we’ll use the example of the tee with the ID letter H between G and J in the system. Now for this we need to consider that the air is moving in two directions, straight through and also turning off into the branch so we need to perform a calculation for both directions.

If we look at the air travelling straight though first, we find the velocity ratio first using the formula velocity out divided by velocity in. In this example the air out is 3.3m/s and the air in is 4m/s which gives us 0.83

Then we perform another calculation to find the area ratio, this uses the formula diameter out squared divided by diameter in squared. In this example the diameter out is 0.24m and the diameter in is 0.33m so if we square them and then divide we get 0.53

Now we look up the fitting we’re using from the manufacturer or the industry body, again link here for that.

Duct tee sizing
Duct tee sizing

In the guides we find two tables the one you use depends on the direction of flow, we’re using the straight direction so we locate that one and then look up each ratio to find our loss coefficient. Here you can see both of the values we calculated fall between vales listed in the table so we need to perform a bilinear interpolation. To save time we’ll just use an online calculator to find that, link here (watch the video to learn how to perform a bilinear interpolation).

We fill out our values and we find the answer of 0.143

Tee pressure loss calculation
Tee pressure loss calculation

Now we calculate the dynamic loss for the straight path through the tee, using the formula co multiplied by rho multiplied by v squared divided by 2. If we drop our values in we get the answer of 0.934 pascals so add that to the table.

Then we can calculate the dynamic loss for the air which turns into the bend. For this we use the same formulas as before. Velocity out didived by velocity in to find our velocity ratio. Then we find the area ratio using the formula diameter out squared divided by diameter in squared. We take our values from our table and use 3.5m/s divided by 4m/s to get 0.875 for the velocity ratio and we use 0.26m squared divided by 0.33m squared to get 0.62 for the area ratio.

Tee fitting loss bend
Tee fitting loss bend

Then we use the bend table for the tee section, again its between the values listed in the table so we have to find the numbers using bilinear interpolation. We drop the values in to get the answer of 0.3645 pascales. So just add that to the table too.

Now repeat that calculation for the other tees and fittings until the table to complete.

Finding the index run – duct sizing

Next we need to find the index run which is the run with the largest pressure drop. It’s usually the longest run but could also be the run with the most fittings.

We find it easily by adding up all the pressure losses from the start to the exit of each branch .

For example to get from A to C we lose 5.04pa
A (1.3pa) + B (1.79pa) + C (1.95pa)

For A to F we lose 8.8pa
A (1.3pa) + B (1.7pa) + D (1.3pa) + E (2.55pa) + F (1.95)

For A to I we lose 10.56
A (1.3pa) + B (1.7pa) + D (1.3pa) + E (1.34pa) + G (2.6pa) + H (0.36pa) + I (1.95pa)

For A to L we lose 12.5pa
A(1.3pa) + B (1.7pa) + D (1.3pa) + E (1.34pa) + G (2.6pa) + H (0.93pa) + J (0.65pa) + K (0.72pa) + L (1.95pa)

Therefore the fan we use must overcome the run with the highest loss, that being A – L with 12.5pa, this is the index run.

Ductwork dampers – system balancing

To balance the system we need to add dampers to each of the branches to ensure equal pressure drop through all to achieve the design flow rates to each room.

We can calculate how much pressure drop each damper needs to provide simply by subtracting the loss of the run from the index run.

A to C is 12.5pa – 5.04pa = 7.46pa

A to F is 12.5pa – 8.8pa = 3.7pa

A to I is 12.5pa – 10.56pa = 1.94pa

And that is our ducting system. We’ll do another tutorial covering additional ways to improve efficiency in ductwork system.

22 COMMENTS

  1. Thank you very much fo this info guys. May you do more lessons on ducting. especially on dumpers, flexible duct calculations, duct risers and toilets ventilation.

  2. This is a great work, it is really well explained and truly beneficial. thanks a lot for this piece. However, I have a question, in calculating the overall pressure drop per duct length. Are we considering the effective length of the duct or just the length of the duct?

    Thank you.

  3. Hi there Paul
    Thank you for this informative explanation and its really helpful. My question is on the selection of the unit size Do I use the total cooling load to select the size of my machine or I have to use the also the data on the duct friction loss to select the unit. Please I need help as I am trying to understand clear how its done.
    Also can you do another illustration on the return duct size and location.
    I would like it as well if you can finish the illustration with diffusers, grills and flexible ducts.
    Thank you so much with your info

  4. Thanks a lot for this is a useful work, it is well explained and really helpful. thanks a lot for this great work. May you do more lessons similar to this series on BMS, SCADA, DCS and its interaction with HVAC systems in the smart buildings.
    Thank you very much for your great work.

  5. I appreciate that you explain to us how the equal friction method is used for medium to large size commercial installation. Personally, I don know much about ductwork, but I think is great to learn more about it. Thank you for helping me learn more about the methods used for ductwork designs.

  6. Hi,

    Thank you for the video, it is well explained. However, please I will like see how grilles and filters affect the external static pressure of a system in your next video.

    Thanks,
    Newton

  7. Hi, thanks for this article. I used this method with the same pressure in all ducts from the main to all the branches with the quantity of air needed, I found out that some duct and branches fall below 2 m/sec. what will happen if I adjust the velocity and the pressure?

  8. So for attaining designed cooling for Room 1 ( 2.4KW OR 0.68 TR) , do we need a flow rate of 457 CFM.
    Pls help me team on this , do we need this much CFM for less than a ton cooling.

  9. Personally, I don know much about ductwork, but I think is great to learn more about it. I appreciate that you explain to us how the equal friction method is used for medium to large size commercial installation. This is great work, it is really well explained and truly beneficial. thanks a lot for this piece.

  10. Another important factor that you may want to take into consideration when it comes to learning how to design a duct system is to determine how much insulation you will want between each section of duct work. This is especially important if you are going from one floor of the building to another within the structure. You also want to make sure that you don’t cross over any pipes or insulation. One way to keep yourself from doing this is by putting insulation on the inside perimeter of the duct and inside any cavities that run through the duct system. Another thing that you will want to keep in mind is that if there is a drain that goes to a lower level than the room that the ducts will be in, then you will need to have a drain to remove excess water before you install your ductwork.

    You also need to keep in mind that any flex ducts that you put in your duct system will need to be sealed with a silicone caulk or some type of sealing agent. If they are not then you could have a leak present that will allow moisture to get inside and cause problems within the walls of your home. Learning how to design a duct system isn’t something that should be done by just anyone, especially if you don’t know what you are doing. You should always consult with an experienced professional before you start working on your HVAC system.

  11. This is really great, Paul, maybe you can help tell me what I am doing wrong.

    I have a 2-room basement (13cm concrete, insulated inc floor).
    – The large room (RM1) is 24.8m3, and we hang the clothes and i have my computer rack in there.
    – The small room (RM2) is 8.25m3 and contains the boiler and clothes dryer
    – Both rooms have an inward tilt 1m*.5m window, to a light shaft
    – RM2 has a 100mm pipe above the window through 13cm concrete + 6cm of insulation

    If I close the door to RM1 from the stairwell (opposite side of windows), the temp rises to 32deg overnight. If I open the door, it drops back to 24deg.

    I installed a 150mm inline duct fan in RM1 with a rating of 540m3/h.
    – the outlet is connected as follows;
    50cm x150m duct, 45degx150mm, 50cm duct, 45degx150mm, 100mm reducer connected directly to the 19cm 100mm pipe through the wall with a 100mm 45deg weather cover outlet in the light shaft.

    – the inlet is connected to a 60cm 150mm silencer, 50cm duct 150mm, 125 reducer, 45deg 125mm, 10cmx 125mm, 45deg 125mm and 20cmx125mm through the wall of RM2 and RM1. The inlet is open at the wall inside RM1. (I tried connecting multiple ducts to 4 points in RM1, but that had negative consequences).
    * all ducts are rigid (white) PVC.
    The silencer reduced the jet noise by about 20db, so it is now around 55-60db from 75-80db before.

    But the current setup means the temp still rises to 28-29deg overnight, and if I open the door to RM1 it rapidly drops back to 24deg. (the desired temp range).

    The computer rack has 4 fans in the roof but has a dispersion cover over that. The only thing I can think to do now is, remove the dispersion top and make a funnel to cover the fans and connect directly to the duct, but this would mean a length of about 3.5m of 125mm duct from the RM1/2 wall. I think this would reduce the performance of the fan no?

    Would really appreciate your insight/suggestions how i could get to the desired temp range in the RM2.

  12. This is nicely written up, like how you have put clear units on all the things, and you have a nice way of explaining everything.

  13. MANY THANKS,

    I normally do DHW and HTG and use Diversity factor for design the residential. The branch flow rate design for air is similar to water.Have you thought about this?
    I am not member of CIBSE and sometimes buy their CPD and other PDfs. They are not cheap. Is there any way to find those tables and charts anywhere? however, I am already grateful for the work you have done here.

LEAVE A REPLY

Please enter your comment!
Please enter your name here